TOSHIBA 2N3A3620-B CPU模块
TOSHIBA 2N3A3620-B CPU模块
2N3A3110-C东芝模块TOSHIBA 2N3A3110-C,2N3A320-B,2N3A8130-A,2N3A3120-D东芝模块,东艺IGCT模块东芝集团创立于1875年,致力于为人类和地球的明天而努力奋斗,力争成为能创造丰富的价值并能为全人类的生活、文化作贡献的企业集团,东芝集团业务领域包括数码产品、电子元器件、社会基础设备、家电等
东芝模块TOSHIBA 2N3A3110-C 安装调试
确保2N3A3110-C 在设定地址前完成电力排线
2N3A3110-C 先送内机电源再送外机电源,如果在开启室内机之前开启室外机,外机P.C板上7段显示码会显示E19,直至开启室内机电源。
自动寻址可能会花费十分钟时间 (正常为5分钟)
.自动寻址要求在室外机操作。 (仅打开电源不能自动寻址。)自动寻址会使用到室外机P.C.板界面上的SW15按键
1.首先送上室内机电源,然后再送室外机电源。
2.电源送上后确认室外主机P.C.板界面上7段显示板显示 U.1.L08(此时U.1.闪烁)
3.按下SW15(7段显示板有了变化松开,正常3秒左右)开始自动寻址(通常为5分钟)。4.7段显示指示Auto1然后Auto2到Auto3
指示 U.1.-(U.1.闪烁)开始在显示器上闪烁后。闪烁停止显示器显示 U.1.一(U.1.灯常亮),设定完成调试前准备工作
1.确定保压正常,系统无漏。
2.算好铜管每米追加量与机组的修正量
3.液管与气管阀门打开。
TOSHIBA 2N3A3620-B CPU模块
2N3A3110-C Toshiba module Toshiba 2N3110-C, 2N3A320-B, 2N3A8130-A,2N3A3120-D Toshiba module, Dongyi IGCT module Toshiba Group was founded in 1875, and is committed to working hard for the future of mankind and the earth, striving to become an enterprise that can create rich values and contribute to the life and culture of all mankind.
Installation and debugging of Toshiba module TOSHIBA 2N3A3110-C
Ensure that 2N3A3110-C completes the power cable arrangement before setting the address.
2N3A3110-C sends the internal power supply first and then the external power supply. If the outdoor unit is turned on before the indoor unit is turned on, the 7-segment display code on the P.C board of the external unit will display E19 until the indoor unit is turned on.
Automatic addressing may take ten minutes (normally five minutes).
Automatic addressing requires operation in the outdoor unit. (Only turning on the power supply cannot automatically address. ) Automatic addressing will use SW15 button on the interface of outdoor unit P.C. board.
1. First send the indoor power supply, and then send the outdoor power supply.
2. After the power supply is delivered, confirm that the 7-segment display panel on the P.C. panel interface of outdoor host machine displays U.1.L08 (U.1. flashes at this time).
3. Press SW15 (the 7-segment display board has been changed and released, which is normal for about 3 seconds) to start automatic addressing (usually 5 minutes). The display in paragraph 4.7 indicates Auto1 and then Auto2 to Auto3.
After the indication U.1.-(U.1. flashing) starts flashing on the display. Flashing stops the display to display U.1.1 (U.1. The light is always on), and it is set to complete the preparation work before debugging.
1. Make sure that the pressure maintaining is normal and the system has no leakage.
2. Calculate the additional amount of copper tube per meter and the correction amount of the unit.
3. Open the valve of liquid pipe and trachea.
TOSHIBA 2N3A3620-B CPU模块